Fire Alarm Control Panel EvoxX CF

EvoxX CF

Fire alarm control panel EvoxX CF is a compact control panel for industrial and commercial fire detection systems. It supports decentralised system design, loop-based device monitoring, event logging and networked fire alarm architecture. Also, the basic configuration supports two loop circuits with up to 500 elements, while expansion options can support additional loops, networking, universal interface or input/output modules. As a result, it suits sites that need structured fire alarm monitoring, device-level control and scalable plant safety infrastructure.

  • Compact control panel
  • Up to 4 loops per panel
  • Event log up to 65,000
  • LAN / WAN networking
  • Remote monitoring option

Loop design guidance

Device count review

Panel compatibility support

Network planning help

Installation backup

Still Confused What to Buy?
Need help deciding? Download resources to know more about the product.
  • Compact fire alarm control panel
  • Decentralised system design
  • Basic configuration with two loop circuits
  • Maximum 500 elements in basic configuration
  • Expansion slot for system scalability
  • Optional module for two additional loop circuits
  • Up to 4 loops per control panel
  • Optional network module support
  • Optional universal interface module
  • Optional input/output module
  • Event log memory for up to 65,000 events
  • Freely programmable controllers and algorithms
  • Can be networked over copper cable or optic fibre connections
  • Up to 16 sub control units can form an Integral LAN mesh network
  • Larger systems can use Integral WAN fire alarm network architecture
  • Optional remote monitoring over the Internet
  • Integrated LAN interface
  • Wireless service interface
  • Various protocols for connection to building management systems
  • Built-in Integral MAP operating panel
  • Operating panel available in more than 20 language versions
  • Available in different case types, with or without protocol printer, or black box edition
  • Industrial fire alarm control systems
  • Addressable fire detection systems
  • Control room fire alarm monitoring
  • Electrical room fire detection systems
  • Warehouse and store alarm monitoring
  • Utility area fire alarm systems
  • Commercial building fire detection
  • Multi-zone plant fire alarm systems
  • Fire detector and manual call point monitoring
  • Hooter and alarm output control
  • Building management system integration
  • Networked fire alarm architecture
  • Product Type: Fire Alarm Control Panel
  • Model: Integral EvoxX CF
  • Application Fit: Fire detection and alarm monitoring for industrial and commercial systems
  • System Design: Compact control panel with decentralised system design
  • Basic Loop Capacity: 2 loop circuits
  • Maximum Elements in Basic Configuration: 500 elements
  • Maximum Loop Capacity: Up to 4 loops per control panel with expansion
  • Expansion Slot Options: Network module, module for two additional loop circuits, universal interface module, input/output module
  • Networking: Copper cable or optic fibre connection
  • LAN Networking: Up to 16 sub control units in Integral LAN mesh network
  • WAN Networking: Multiple LAN networks can be connected to Integral WAN fire alarm network
  • Event Log Memory: Up to 65,000 events
  • Remote Monitoring: Optional access over Intranet or Internet
  • Building Management Integration: Various protocols available
  • LAN Interface: Integrated LAN interface
  • Service Interface: Wireless service interface
  • Operating Panel: Integral MAP operating panel
  • Operating Panel Languages: More than 20 language versions
  • Mains Supply Voltage: 110 V AC -15% to 230 V AC +10%
  • Power Supply Frequency: 47 to 63 Hz
  • Input Power: Maximum 160 W
  • Output Power: Maximum 115 W
  • Output Voltage: 26.3 V DC at +50°C to 28.3 V DC at 0°C
  • Output Current: Maximum 4 A
  • Quiescent Current: 72 mA with operating panel and without printer
  • Usable Rechargeable Batteries: 2 pcs. 12 V / 15 to 18 Ah in series
  • Emergency Power Supply: 72 hours normal operation plus 0.5 hour alarm
  • Protection Class: IP30
  • Ambient Temperature: -5°C to +50°C
  • Relative Humidity: 5% to 95%, non-condensing
  • Air Pressure: ≥80 kPa, up to 2000 m above sea level
  • Case Material: Sheet steel
  • Case Colour: Red RAL 3000
  • Dimensions: 400 × 445 × 140 mm, H × W × D
  • Weight: 19 kg including rechargeable batteries
  • Approval Reference: VdS approval G200081
  • Declaration of Performance: CPR-20-21-002

    Comprehensive Services Using This Product

    From installation to ongoing support, we’re with you every step of the way.

    What Customers Say About Us

    Trusted Engineering Support

    The team provided clear technical guidance and practical solutions. Execution was smooth and well coordinated throughout.

    Mr. Vivek NairGeneral Manager – Operations, Cement Industry
    Dependable Technical Partner

    Their approach was systematic and aligned with our plant needs. Overall experience with product and service has been positive.

    Ms. Kavita RaoSenior Manager – Maintenance, Steel Sector
    Application-Focused Solutions

    They understood our process conditions before recommending equipment. Support during installation was handled professionally.

    Mr. Rohan MehtaProject Lead – Power Plant
    Consistent Service Delivery

    Product performance has been stable in regular operations. The support team responds in a timely manner.

    Mr. Anil DeshmukhInstrumentation Head, Process Manufacturing

    Insights & News

    Ensuring Environmental Compliance with CEMS: A Step Ahead
    Learn how Continuous Emission Monitoring Systems (CEMS) help industries stay compliant with environmental norms, providing real-time emission data, remote monitoring, and actionable insights for sustainable and responsible manufacturing.
    How Predictive Maintenance is Transforming Industrial Efficiency
    Discover how advanced monitoring tools like vibration and ultrasound solutions are helping industries move from reactive to predictive maintenance—reducing downtime, extending equipment life, and optimizing productivity across critical operations.

    Clients Who Have Transformed Their Operations with This Product

    Logo
    Logo
    Logo
    Logo
    Logo
    Logo
    Logo
    Logo
    Logo
    Logo
    Logo

    Frequently Asked Questions

    EvoxX CF is used as a fire alarm control panel for monitoring and managing fire detectors, manual call points, alarm devices and fire alarm events in industrial and commercial systems.
    The basic configuration supports two loop circuits. With expansion, the panel can support up to 4 loops per control panel.
    The basic configuration supports up to 500 elements across two loop circuits.
    Yes. EvoxX CF can be networked using copper cable or optic fibre connections. Up to 16 sub control units can form an Integral LAN mesh network, and larger systems can use Integral WAN architecture.
    Yes. Optional remote monitoring over Intranet or Internet is available, depending on system design and configuration.
    Yes. It supports event log memory with capacity for up to 65,000 events.
    Users should check detector count, manual call point count, loop requirement, alarm output need, network requirement, building management integration, battery backup and future expansion plan before selection.

    Download Resources

    Send Us Your Requirements

    We will respond you soon.

    Share:
    Send Us Your Requirements

    Fill the form to download resources

    Send Us Your Requirements

    We will respond you soon.