| Input |
Type (Selectable) |
T/C: J/K/R/S/T/B/E/N/W/PL11/U/L in trimmable ranges from (-) 199.9 – 2320 ºC |
| RTD: Pt 100, 3 wire,(-)199.9 - 600 ºC |
| DC mA: 4- 20 mA / 0- 20mA, Scalable |
| DCV: (-) 10-0-10mV /0 – 10mV /0 – 50mV /10 – 50mV /0 – 1V /1 – 5V /0 – 10V DC, Scalable |
| Sampling time |
0.5 Sec |
| Input Impedance |
T / C: > 20 Meg ohms |
| MA: <2.5 ohms |
| Display |
PV/SV |
Type, Color |
2×4 digit, 7 segment LED; PV – Red, SV - Green |
| Size |
PV |
14 mm (P-909. P-907. P-906), 10 mm (P-908),7 mm (P-904) |
| SV |
10 mm (P-909, P-908,. P-907), 7 mm (P-906,P-904) |
| Accuracy |
±0.2% FS ± 1 digit typical, ± 0.5% F.S. max |
| Resolution |
T/C: 1°C (0.1°C for models with range upto 400°C |
| RTD: 0.1°C |
| Analog Input: 1/0.1/0.01/0.001 |
| MV |
Control output/Valve position |
Green Colour 10 LED horizontal bar graph (Except P-906 & P-904) |
| Status |
Out 1, out 2 |
Green LED |
| Alarms(AL1,AL2,AL3) |
Red LED |
| AT, Manual, Program |
Orange LED |
| Control output (Selectable limit 0-100%) |
Relay |
Output 1: SPDT, 3A/ 240 VAC, resistive load(SPDT in P-904/Other models with Out 2 or AL 3) |
| Output 2: SPST, 3A/ 240 VAC, resistive load |
| Voltage Pulse for SSR |
20 V DC ±10%, max current 20 mA |
| mA DC |
4-20 mA, adjustable between 0-20 mA;load: 600 ohms(max) |
| Servo motor drive |
Open loop, 2 Relays; SPST, 3A/240 VAC; option 110A/240 VAC;resistive load.
Note: Separate position indicator to accept feedback potentiometer for Valve position available.
|
| 1ph/ 3ph SCR Control Trigger Pulse |
Pulse Transformer, Zero cross/ Phase control |
| PID |
Proportional Band |
0-200% FS |
| Integral Time |
0-3600 sec |
| Derivative time |
0-900 sec |
| Alarm |
Upto 3 Alarms |
Relay: SPST, 3A/ 240VAC resistive load in 17 selectable modes(High/ Low/ Deviation/ Band with or without 1st time alarm inhibit function & delay) |
| Auto/Manual |
Bumpless Switching |
Standard (Except P-904) |
| Remote input |
Setpoint |
4-20 mA DC; Adjustable between 0-20 mA |
| Retransmission |
PV/SV/MV transmitter output |
4-20 mA DC; Adjustable between 0-20 mA |
| Communication |
Digital Interface |
RS 485 / RS 232 |
| Power Supply output |
For External 2-wire transmitter |
24 V DC, option (Except P-904 & P-907) |
| Power |
Range |
85-264 VAC, 50/60 Hz; 24 V DC ±20% (optional) |
| Consumption |
<10VA |
| Size |
Front /Panel cutout (W×H)mm |
P-909 96×96 / 90.5×90.5 P-907 72×72 / 68.5×68.5 |
| P-908 48×96 / 44.5×90.5 P-906 96×48 / 90.5×44.5 |
| P-904 48×48 / 44.5×44.5 |
| Depth |
80 mm behind panel, overall 96 mm |
| Ambient |
Temp., Humidity |
0-50 °C 30-95% RH (non condensing) |
| Memory |
Non-Volatile |
EEPROM, data storage >10 years without battery |
| Weight |
Approximately |
AP -909 : 320 g; P-909 :320g; P -908 : 250 g; P -907: 250 g; P -906 : 250 g; P -904 : 150 g |